Mitsubishi Electric Artisan MELSEC-Q Series Manual page 55

General-purpose programmable controllers, large/small
Table of Contents

Advertisement

2.2 Replace AnS/QnAS (Small Type) Series with Q Series
(2) Compatibility of AnS size version Q Series large type base unit with the upgrade tool
The following table shows the compatibility of AnS size version Q Series large type base unit with the upgrade
tool manufactured by Mitsubishi Electric Engineering Co., Ltd. when replacing existing A (Small Type) Series
modules with Q Series modules.
Slot width of base unit
Power supply module
CPU module
Mountable
module*
5
• I/O module
• Intelligent function
module
For terminal block type 16-point I/O module (1-slot type)
For terminal block type 16-point I/O module (2-slot type)
Conversion
adapter*
5
For high-speed counter module
For analog module (1-slot type)
Connection of QA/QA1S extension base unit*
*1: AnS size version Q Series large type base units, Q Series base units (standard products) and Q Series
large base units can be used together.
*2: Mount a Q Series base unit (standard product) on the base adapter manufactured by Mitsubishi Electric
Engineering Co., Ltd.
*3: Q00UJCPU is not compatible.
*4: The following modules cannot be used.
• A module whose height is more than 98 mm.
• A module with a bracket on top.
• A module with a protrusion, such as a connector, on
the bottom.
• A module onto which Q7BAT-SET is mounted.
* Example
Q66AD-DG, Q66DA-G, Q68AD-G, Q68RD3-G, Q68TD-G-H02, Q64AD2DA, QD75M1, QD75MH1,
QD75M2, QD75MH2, QD75M4, QD75MH4, or QJ71WS96 with Q7BAT-SET mounted.
*5: Since the adapters are mounted on Q Series modules, the specifications and functions are same as those
of the Q Series modules. (Please check the transition handbook, since the specifications and functions
are different from those of A (Small type) Series module)
*6: The AnS size version Q Series large type blank cover (QG69LS) must be mounted.
*7: Only High Performance Model QCPUs can be connected to the QA/QA1S extension base unit.
This cannot be used with the MELSECNET/H remote I/O station, etc.
*8: If the size of the copper wire connected to the terminal block is larger than 1.25 mm
mount the conversion adapter.
In this case, secure wiring space by leaving empty slots in between modules. For example, mount modules
on slot No. 0, 2, 4, 6, 8, and leave slot No. 1, 3, 5, 7 empty. Mount a blank cover QG60 on the empty slots.
If there are not enough slots, consider using the AnS size version Q Series large type base unit.
*9: Applies when using replacing the existing A (Small Type) module with the two Q Series modules, and using
the existing wiring terminal block with the conversion adapter.
(Example) A1SX20 -> QX28 x 2 modules, A1SY60(E) -> QY68A x 2 modules
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Item
Q Series standard power supply module
Basic model QCPU
High Performance model QCPU
Process CPU
Universal model QCPU
Multi-CPU configuration
MELSECNET/H remote I/O module
Q Series 1-slot module *
4
Q Series 2-slot occupying module
7
AnS size version
Q Series large type base unit*
Same width as the A (Large Type)
Series base unit (34.5 mm)
×
×
○ *
3
×
*6
×
*6
×
*6
*6
○: Applicable (Mountable), ×: Not Applicable (Not mountable)
MELSEC-AnS Series module
34.5
52
Base adapter (Upgrade tool)*
1
Same width as Q Series base unit
(27.4 mm)
*9
*8
*8
MELSEC-Q Series module
Replace with the
terminal block
cover enclosed
with the
conversion
adapter.
27.4
, it may be difficult to
2
2