Mitsubishi Electric Artisan MELSEC-Q Series Manual page 36

General-purpose programmable controllers, large/small
Table of Contents

Advertisement

(f) Specifications comparison between AY13 and A6TE2-16SRN
Item
Number of output points
Isolation method
24 V DC/2 A (resistive load)/point,
Rated switching
240 V AC/2 A (cos Ф =1)/point,
voltage/current
Minimum switching load
Maximum switching
voltage
ON to OFF
Response
time
OFF to ON
Mechanical
Rated switching voltage/current
Life
(cos Ф =0.7): 200,000 times or more
Electrical
(cos Ф =0.35): 200,000 times or more
(L/R=7 ms): 200,000 times or more
Maximum switching
frequency
Common terminal
arrangement
Operation indicator
Voltage
External
Ripple voltage: 4 Vp-p or less
power
supply
Current
(TYP. 24 V DC, all points ON)
External connections
Applicable wire size
Applicable crimping
terminal
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
AY13
32 points
Photocoupler
24 V DC/2 A (resistive load)/point,
5 A/common
5 V DC 1 mA
264 V AC
125 V DC
10 ms or less
12 ms or less
20 million times or more
Rated switching voltage/current
load: 200,000 times or more
200 V AC 1.5 A, 240 V AC 1 A
(cos Ф =0.7): 100,000 times or more
200 V AC 0.7 A, 240 V AC 0.5 A
(cos Ф =0.35): 100,000 times or more
24 V DC 1 A, 100 V DC 0.1 A
3600 times/hour
8 points/common
(common terminals:
TB9, TB18, TB27, TB36)
ON indication (LED)
24 V DC ±10%
Ripple voltage: 4 Vp-p or less
290 mA
(TYP. 24 V DC, all points ON)
38-point terminal block
38-point screw terminal block
connector (M3 × 6 screws)
0.75 to 2 mm
2
R1.25-3, R2-3,
RAV1.25-3, RAV2-3
2.1 Replace A/QnA (Large Type) Series with Q Series
Compati-
A6TE2-16SRN
16 points
Relay
240 V AC/2 A (cos Ф =1)/point,
8 A/common
5 V DC 1 mA
264 V AC
125 V DC
10 ms or less
12 ms or less
20 million times or more
load: 100,000 times or more
200 V AC 1.5 A, 240 V AC 1 A
200 V AC 0.7 A, 240 V AC 0.5 A
24 V DC 1 A, 100 V DC 0.1 A
(L/R=7 ms): 100,000 times or more
3600 times/hour
8 points/common
(common terminals:
TB19, TB21)
ON indication (LED)
24 V DC ±10%
350 mA
(M3 screw) (M3 × 6 screws)
0.75 to 1.25 mm
2
R1.25-3, R1.25-MS3,
R1.25-B3A, R1.25-C3A,
RAV1.25-3, RAV1.25-MS3,
RAV1.25-B3A
33
○: Compatible, △: Partially changed
Remarks
bility
Use two A6TE2-16SRN modules
when using more than 16 points.
The isolation method differs, but the
isolation performance is equivalent.
The electrical life of
the A6TE2-16SRN is half of
the AY13's life. However, the relay
for the A6TE2-16SRN can be
replaced.
The supplied current value will be
larger.
Wiring modification is required.