Mitsubishi Electric Artisan MELSEC-Q Series Manual page 184

General-purpose programmable controllers, large/small
Table of Contents

Advertisement

(1) Examples of replacement of A (Large Type) modules with Q Series modules
Existing module
Module model
AX40
AX40-UL (Positive common)
AX41
(Positive common)
AX41-UL
(Positive common)
AX41-S1
(Positive common)
AX42 (Positive common)
AX42-S1 (Positive common)
AX50 (Positive common)
AX50-S1
(Shared by positive common
and negative common types)
AX60 (Positive common)
AX60-S1
(Shared by positive common
and negative common types)
AX70
(Shared by positive common
and negative common types)
AX71
(Shared by positive common
and negative common types)
AX80 (Negative common)
AX80E (Negative common)
AX81
(Negative common)
AX81B (Shared by positive
and negative common types,
with wire breakage detection)
AX81-S1
(Shared by positive common
and negative common types)
AX81-S2
(Negative common)
AX81-S3
(Negative common)
AX82
(Negative common)
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Working conditions
Common
Module model
Working
terminal
voltage
arrangement
24 V
Positive
QX40
12 V
Positive
QX70
QX41
24 V
Positive
QX41-S2
12 V
Common
QX71
QX41-S1
24 V
Positive
QX41-S2
12 V
Common
QX71
QX42
24 V
Positive
QX41-S2 (2 modules required)
12 V
Positive
QX72
24 V
Positive
QX42-S1
Positive
48 V
QX50
Common
100 V
Positive
QX40-S1
24 V
Negative
QX80
5/12 V
Common
QX70
Positive
QX41-S1
24 V
Negative
QX81-S2
5/12 V
Common
QX71
24 V
Negative
QX80
5/12 V
Common
QX70
QX81
24 V
Negative
QX81-S2
12 V
Common
QX71
24 V
Positive
QX41-S1
QX81
24 V
Negative
QX81-S2
12 V
Common
QX71
48 V
QX50 (2 modules required)
Negative
60 V
QX81
24 V
Negative
QX81-S2
12 V
Common
QX71
QX82
24 V
Negative
QX81-S2 (2 modules required)
12 V
Common
QX72
181
10.1 Select replacement module for DC input module
Replacement module
Conversion adapter
ERNT-AQTX40
ERNT-AQTX41
ERNT-AQTX41
ERNT-AQTX40
(No replacement model)
ERNT-AQTX40
ERNT-AQTX80
ERNT-AQTX40
ERNT-AQTX41
ERNT-AQTX81
ERNT-AQTX41
ERNT-AQTX80
ERNT-AQTX40
ERNT-AQTX81
ERNT-AQTX41
(No replacement model)
ERNT-AQTX41
ERNT-AQTX81
ERNT-AQTX41
(No replacement model)
ERNT-AQTX81
ERNT-AQTX41
Remarks
• Terminal block -> 40-pin connector
• Rated current: Approx. 4 mA
• Terminal block -> 40-pin connector
• Rated current: Approx. 6 mA
• Terminal block -> 40-pin connector
• Terminal block -> 40-pin connector
• Rated current: Approx. 4 mA
• Terminal block -> 40-pin connector
• Rated current: Approx. 6 mA
• Terminal block -> 40-pin connector
• Rated current: Approx. 6 mA
• Examine whether to replace with
QX40 and FA-TH16X100D31L
• Terminal block -> D-sub 37-pin connector
• 5 V DC: AX80 only
• Rated current: Approx. 4 mA
• Terminal block -> D-sub 37-pin connector
• Rated current: Approx. 6 mA
• Terminal block -> D-sub 37-pin connector
• Terminal block -> 40-pin connector
• Examine whether to replace with
QX81.
• Terminal block -> 40-pin connector
• Rated current: Approx. 4 mA
• Terminal block -> D-sub 37-pin connector
• Rated current: Approx. 6 mA
• Terminal block -> D-sub 37-pin connector
• Terminal block -> 40-pin connector
• Examine whether to replace with
QX81 and install an 8.2-kΩ
resistor (1 W or more) in series
on the external signal line.
• Rated current: Approx. 4 mA
• Terminal block -> D-sub 37-pin connector
• Rated current: Approx. 6 mA
• Terminal block -> D-sub 37-pin connector
• Terminal block -> 40-pin connector
• Rated current: Approx. 4 mA
• D-sub 37-pin connector -> 40-pin connector
• Rated current: Approx. 6 mA
• D-sub 37-pin connector -> 40-pin connector

Advertisement

Table of Contents
loading

Table of Contents