7.5 Method for maintaining existing addresses when replacing MELSECNET/MINI(-S3) with CC-Link

7.5 Method for maintaining existing addresses when replacing MELSECNET/MINI(-S3)
with CC-Link
The existing MELSECNET/MINI(-S3) and the CC-Link differ in the number of occupied points per
station: the former has 8 points per station, and the latter 32 points.
When the existing and new modules differ in the number of occupied points or the number of the
existing modules differs from that of the new modules, it is necessary to change the addresses to be
used in the sequence program. However, the existing addresses can be maintained by transferring
input/output data using the existing address of each station (module) by FROM/TO instructions without
using the CC-Link auto refresh function.
● Replacement example
(1) Number of occupied points per station
The number of occupied points per existing MELSECNET/MINI(-S3) station is 8. A module with
more than 8 points requires more than one station.
*Example of existing configuration
A61P
ACPU
A35B
*Example of new configuration
Q61P
QCPU
Q33B
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
AJ71PT
Input/output
32-S3
module
AX11C
Station No.1
(4 stations,
32 points occupied)
32 points occupied)
(X100 to X11F)
MELSECNET/MINI(-S3)
AJ65SBTB2N
QJ61BT
Input/output
11N
module
Station No.1
(X100 to X10F)
CC-Link
AX41C
AJ35TB2-16D
Station No.5
Station No.9
(4 stations,
(2 stations,
16 points occupied)
(X120 to X13F)
(X140 to X14F)
AX11C is replaced with:
AX41C is replaced with:
AJ65SBTB2N
-16A
-16A
Station No.2
(X110 to X11F)
AY13C is replaced with:
AJ65DBTB1
-32R
Station No.7
(Y170 to Y18F)
152
AX10Y10C
AY13C
Station No.11
Station No.15
(4 stations,
(4 stations,
32 points occupied)
32 points occupied)
(X150 to X15F)
(Y160 to Y16F)
(Y170 to Y18F)
AJ35TB2-16D is
replaced with:
AJ65DBTB1
AJ65SBTB3
-32D
-16D
Station No.3
Station No.4
(X120 to X13F)
(X140 to X14F)
AX10Y10C is replaced with:
AJ65SBTB2N
AJ65SBTB2N
-16R
-16A
Station No.6
Station No.5
(Y160 to Y16F)
(X150 to X15F)