Download  Print this page

Mitsubishi Electric Artisan MELSEC-Q Series Manual Page 76

General-purpose programmable controllers, large/small.
Hide thumbs

Advertisement

(2) Module selection example
Product name
Power supply module (for main base unit)
CPU module
Main base unit
CC-Link master module
MELSECNET/10 network module
Ethernet module
Extension base unit
Power supply module (for extension base unit)
Extension cable
Input module
Output module
Analog input module
Analog output module
Tip
• The following A (Large Type) modules cannot be used with QCPU.
These modules must be replaced with those compatible with QCPU.
• CC-Link master/local module
• MELSECNET/10 network module
• Ethernet module
• Computer link module etc.
• After replacing the module, use the parameter I/O assignment and set so that the existing module addresses
are not changed.
• The QA6 B extension base units and QA1S6 B extension base units are only compatible with High
Performance Model QCPU or Universal Model QCPU (first five digits of serial No. "13102" or higher).
Basic Model QCPUs, Process CPUs, Redundant CPUs, Safety CPUs, and Remote I/O Stations are not
compatible.
• For precautions and restrictions when using QA6 B extension base unit, refer to "QA65B/QA68B Extension
Base Unit User's Manual".
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
3.1 Replace A/QnA (Large Type) Series with Q Series
Existing module
N/A
A3NCPU
A38B
AJ61BT11
AJ71BR11
AJ71E71N3-T
N/A
A61P
N/A
AX41
AY10
A68AD
A68DAI-S1
73
Replacement module
-
Q61P
1
Q06UDHCPU
1
Q35B
1
QJ61BT11N
1
QJ71BR11
1
QJ71E71-100
-
QA68B
1
Utilize existing module
-
QC06B
1
Utilize existing module
1
Utilize existing module
2
Utilize existing module
1
Utilize existing module
1
1
1
1
1
1
1
-
1
-
-
-
-

Advertisement