7.5 Method for maintaining existing addresses when replacing MELSECNET/MINI(-S3) with CC-Link
(2) Method for maintaining existing addresses
The existing addresses can be maintained by transferring transmitted and received data by FROM/
TO instructions for each station without auto refresh setting.
The CC-Link communication conditions including the station information must be set by the
parameters.
(3) FROM/TO instructions sample program for transfer of transmitted and received data
(1) Address allocation table
Buffer memory
address on input
Station No.1
Station No.2
Station No.3
Station No.4
Station No.5
Station No.6
Station No.7
* Sample program
Data transfer
Command 1
Data transfer
Command 2
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Buffer memory
address on
side
output side
E0
E1
E2
E3
E4
E5
E6
E7
E8
E9
16A
16B
16C
16D
153
Model name of
Devices to be
replacement
used by FROM/
module
TO instructions
AJ65SBTB2N-16A
X100 to 10F
AJ65SBTB2N-16A
X110 to 11F
AJ65DBTB1-32D
X120 to 13F
AJ65SBTB3-16D
X140 to 14F
AJ65SBTB2N-16A
X150 to 15F
AJ65SBTB2N-16R
Y160 to 16F
AJ65DBTB1-32R
Y170 to 18F
Receipt of input data to the first module mounted in place of
the existing AX11C
Receipt of input data to the second module mounted in place
of the existing AX11C
Receipt of input data to the module mounted in place of
the existing AX41C
Receipt of input data to the module mounted in place of
the existing AJ35TB2-16D
Receipt of input data to the module mounted in place of
the existing AX10Y10C on the input side
Sending of output data from the module mounted in place of
the existing AX10Y10C on the output side
Sending of output data from the module mounted in place of
the existing AY13C
Device to be used for
auto refresh setting
X100 to 11F
(X110 to 11F: Not in use)
X120 to 13F
(X130 to 13F: Not in use)
X140 to 15F
X160 to 17F
(X170 to 17F: Not in use)
X180 to 19F
(X190 to 19F: Not in use)
Y1A0 to 1BF
(Y1B0 to 1BF: Not in use)
Y1C0 to 1DF