Mitsubishi Electric Artisan MELSEC-Q Series Manual page 164

General-purpose programmable controllers, large/small
Table of Contents

Advertisement

8.1 Replace AD75(P/M) with QD75(P/D/M/MH) while utilizing existing positioning parameters and data
Step 5
Write all positioning parameters and data, including modified data, to the "QD75 using GX Configurator-QP".
Write to module/read from module/verify module data
Write to Flash ROM
Tip
• To use GX Configurator-AP data in GX Configurator-QP, it is necessary to save the file in a format that can
be read by GX Configurator-QP. Files saved in GX Configurator-AP format cannot be read by GX
Configurator-QP.
• Due to specification differences between the AD75 and QD75, some positioning parameters may require
setting changes. Refer to the related manuals for details on the modifications. Note that positioning data
does not require any modifications.
• Related manuals
(a) AD75
A1SD75P1-S3/P2-S3/P3-S3, AD75P1-S3/P2-S3/P3-S3 Positioning Module
User's Manual (Details)
A1SD75M1/M2/M3, AD75M1/M2/75M Positioning Module User's Manual (Details)
GX Configurator-AP Version 1 Operating Manual
(b) QD75
Type QD75P/QD75D Positioning Module User's Manual (Details)
Type QD75M Positioning Module User's Manual (Details)
Type QD75MH Positioning Module User's Manual (Details)
GX Configurator-QP Version 2 Operating Manual
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Via QCPU, Q Series compatible serial
communication module, or
MELSECNET/H network remote I/O
module*
*Only when directly connected to the
remote I/O module.
Title
Title
Buffer memory
Parameters
Servo parameters
Positioning data
Block start data
Flash ROM
Parameters
Servo parameters
Positioning data
Block start data