4.5 Replace MELSECNET/MINI(-S3) with CC-Link
4.5.3 Replace MELSECNET/MINI(-S3) remote I/O station (building block type: AJ72PT35) with
MELSECNET/H using the existing external wiring
Solution and Benefit
• MELSECNET/H (remote I/O network) can utilize Q Series large type base unit. Wiring time can be
reduced by utilizing the external wiring of MELSECNET/MINI remote I/O station, which consists of
existing building block type I/O modules.
• Program modification is not required because the number of occupied points are the same for
each I/O module to be replaced. Therefore, programming time and debugging time after the
replacement is reduced.
● Instructions
(1) Replace the existing MELSECNET/MINI(-S3) with MELSECNET/H (remote I/O network).
Install new network cables: optical cable (loop) or coaxial cable (bus).
(Optical cables are used for the following example.)
(2) When the I/O module of the existing MELSECNET/MINI(-S3) remote I/O station is of terminal block type,
utilize the existing terminal block with the external wiring through a Q Series large type base unit and the
following products.
• Q Series large type I/O modules
• Q Series I/O modules + upgrade tool manufactured by Mitsubishi Electric Engineering Co., Ltd.
(3) In MELSECNET/H (remote I/O network) network parameter, set the master station side devices to be the
same as the ones assigned to the existing MELSECNET/MINI in order to avoid program modification.
(1) System configuration example
Current configuration
MELSECNET/MINI master station
A35B
Station number: 1 Number of occupied stations:
16 (number of input/output points: 128)
A35B
Station number: 17 Number of occupied stations:
16 (number of input/output points: 128)
A32B
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
MELSECNET/MINI
data link system
After replacement
Q35B
Remote I/O station: Station number 1
Q35BL
Replace
Remote I/O station: Station number 2
Q33B
104
Remote I/O network master station
MELSECNET/H remote
I/O network (optical loop)
QG69L
QX41
QY41P
Existing
Existing
Existing
Existing
terminal
terminal
terminal
terminal
block
block
block
block
Existing
Existing
connector
connector

Advertisement

Table of Contents

   Related Manuals for Mitsubishi Electric Artisan MELSEC-Q Series

   Related Content for Mitsubishi Electric Artisan MELSEC-Q Series

Comments to this Manuals

Symbols: 0
Latest comments: