4.3 Replace MELSECNET containing a remote I/O station with MELSECNET/H
(3) Parameter settings and link data transfer program for the normal station replaced from the remote I/O station
■ MELSECNET/Ethernet network parameter settings
Network type
MNET/H mode(Nor Sta)
Start I/O No.
Network No.
Total stations
Group No.
Station No.
Mode
Online
No sta.inher.para.settings
Refresh para. settings exist
No interrupt settings
■ Refresh parameters
SB Transfer
SW Transfer
Transfer 1
Transfer 2
■ Transfer program between link data (LX/LY) and actual I/O (X/Y)
SM400
0
Always ON
9
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Mdl. 1
Mdl. 2
0100
1
----------
0
----------
----------
----------
----------
----------
----------
----------
Link side
Points
Start
512
SB0000
SB01FF
512
SW0000
SW01FF
256
LX0500
LX05FF
256
LY0500
LY05FF
Mdl. 3
End
Points
<-->
512
<-->
512
<-->
256
<-->
256
BMOV
K4X500
Control
station
receive
data
BMOV
K4X0
Host
station
input module
start address
96
Mdl. 4
PLC side
Start
End
SB0000
SB01FF
SW0000
SW01FF
X500
X5FF
Y500
Y5FF
K4Y0
K16
Host
station
output module
start address
K4Y500
K16
Control
station
receive
data
END