4.2 Replace one of A Series stations with Q Series while retaining MELSECNET(ΙΙ)
● Module selection example
(Local station 1)
Product name
Power supply module
CPU module
Main base unit
Input module
Output module
MELSECNET(ΙΙ) local station data link module
Extension base (for A1S Series module)
Extension Power supply module
(for A1S Series module)
Extension cable
(Local station 3)
Product name
Power supply module
CPU module
Main base unit
Input module
Output module
MELSECNET(ΙΙ) local station data link module
Extension base (for A1S Series module)
Extension cable
*1: QA1S51B is an extension base that does not require a power supply, so if the extension cable is long, a voltage drop could
prevent the specified voltage from being supplied. Always calculate the voltage drop.
*2: QA1S51B only has an IN type extension connector, so it will be the extension final stage. QA6 B (Large Type) extension base
cannot be connected below QA1S51B.
● Local station data link module options
Model
A1SJ71AP23Q
A1SJ71AR23Q
A1SJ71AT23BQ
Tip
1. Except for the local station replaced with the Q Series, modification to the system configuration and
programs are not required.
2. Minimal setup is required, as network parameter settings (excluding link refresh setting) are automatically
detected by the local station data link module. FROM/TO instructions within sequence program (refresh
program) are required to enable send/receive cyclic data.
A sample program to enable send/receive of cyclic data can be created by "A/QnA -> Q conversion
support tool" (which can be downloaded from the MELFANSweb). (Refer to Section 9.2)
3. If slots are left empty in the replacement Q Series CPU after connecting the A (Large Type) extension
base onto which the QA6B extension base unit or QA conversion adapter QA6ADP is connected, the
MELSECNET(II), /B local station data link module can be connected using the A-A1S conversion adapter.
QA1S6B or QA1S51B do not need to be additionally selected in this case.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
A61P
A3ACPUP21
A38B
AX
AY
Embedded in CPU module
N/A
N/A
N/A
A61P
A2NCPU21
A38B
AX
AY
Embedded in CPU module
N/A
N/A
MELSECNET(II) local station data link module for SI optical fiber cable
MELSECNET(II) local station data link module for coaxial cable
MELSECNET/B local station data link module for shielded twisted pair cable
89
Existing module
1
Q61P
1
Q03UDCPU
1
Q38B
QX
QY
1
A1SJ71AP23Q
QA1S65B
A1S61PN
QC06B
Existing module
1
Q61P
1
Q02UCPU
1
Q38B
QX
QY
A1SJ71AP23Q
QA1S51B*
QC06B
Outline
Replacement module
1
1
1
1
1
1
1
Replacement module
1
1
1
1
*
1
1
2
1

Advertisement