The current tap position of the on-load tap-changer is transmitted from the
ECOTAP VPD MD&C controller to the CONTROL PRO controller. No further
settings are necessary for this.
8.9 Parallel operation (optional)
Parallel transformer operation is used to increase the throughput capacity or
short-circuit capacity at one location. The device provides you with specific
functions for regulating transformers.
Compliance with the following general conditions is required for operating
transformers in parallel:
▪ Identical rated voltages
▪ Transformer power ratio (< 3 : 1)
▪ Maximum deviation of short-circuit voltages (U
nected in parallel < 10%
▪ Same number of switching groups
▪ For parallel operation with CAN communication: Current transformers with
the same rated values must be used for all devices operating in parallel
8.9.1 Parallel operation methods
You can undertake parallel operation with various parallel operation meth-
ods.
With the tap synchronization parallel operation method, one voltage regu-
lator works as the master and all others as followers.
T1
Figure 65: Tap synchronization
5252433/02 EN
Master
M
AVR
Tap position
CAN bus
) for transformers con-
K
Follower
AVR
M
®
®
ECOTAP
VPD
CONTROL PRO
T2
97