®
®
178
ECOTAP
VPD
CONTROL PRO
12 Technical data
12.1 Voltage supply
Permissible voltage range
Permissible frequency range
Power consumption
Table 65: Voltage supply
12.2 Voltage measurement and current measurement
Measurement
Voltage measurement
Current measurement
Phase angle
Frequency measurement
Table 66: Technical data for the UI 3 assembly
UI 3
3 phase
U
(RMS): 100 V AC
N
Measuring range (RMS): 19.6...150 V AC
Measuring accuracy (at U
Intrinsic consumption: < 1 VA
Measurement category III in accordance with IEC
61010-2-30
I
: 0.2 / 1 / 5 A
N
Measuring range: 0.01...2.1 · I
Overload capacity: 12.5 A (continuous), 500 A (for 1 s)
Measuring accuracy (at I
Intrinsic consumption: < 1 VA
Measuring accuracy (-25...+70 °C): U
<± 0.3°
f
: 50 / 60 Hz
N
Measuring range: 45...65 Hz
Measuring accuracy (-25...+70 °C): <± 0.03%
5252433/02 EN
12 Technical data
G1 PULS QS3.241
85...276 V AC
88...375 V DC
U
: 100...240 V AC
N
U
: 110...300 V DC
N
50 / 60 Hz
70 W
, -25...+70 °C): <± 0.3%
N
N
, -25...+70 °C): <± 0.5%
N
/I
<± 0.5°; U
x
x
Maschinenfabrik Reinhausen GmbH 2018
/U
x
y
Need help?
Do you have a question about the ECOTAP VPD CONTROL PRO and is the answer not in the manual?