MR TAPCON 230 Quick Manual

MR TAPCON 230 Quick Manual

Voltage
Hide thumbs Also See for TAPCON 230:

Advertisement

Voltage Regulator
TAPCON® 230
Quick Guide
4831166/00

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TAPCON 230 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for MR TAPCON 230

  • Page 1 Voltage Regulator TAPCON® 230 Quick Guide 4831166/00...
  • Page 2 © All rights reserved by Maschinenfabrik Reinhausen Dissemination and reproduction of this document and use and disclosure of its content are strictly prohibited unless expressly permitted. Infringements will result in liability for compensation. All rights reserved in the event of the granting of patents, utility models or designs.
  • Page 3: Table Of Contents

    Table of contents Table of contents Introduction................5 Manufacturer................5 Completeness................5 Supporting documents............... 5 Safekeeping................6 Safety..................7 Hardware.................. 8 Operating controls..............8 Display elements..............10 Functions and settings............13 Setting the language..............13 NORMset................. 14 Control parameters..............17 4.3.1 Setting desired value 1...3..............
  • Page 4 Table of contents Overview of parameters............24...
  • Page 5: Introduction

    1 Introduction Introduction This technical file contains information for quick start-up of the product. It does not provide comprehensive operat- ing instructions. This technical file is intended solely for specially trained and authorized personnel. Manufacturer The product is manufactured by: Maschinenfabrik Reinhausen GmbH Falkensteinstraße 8 93059 Regensburg, Germany...
  • Page 6: Safekeeping

    1 Introduction Also observe generally valid legislation, standards and guidelines as well as specifications on accident preven- tion and environmental protection in the respective coun- try of use. Safekeeping This technical file and all supporting documents must be kept ready at hand and accessible for future use at all times.
  • Page 7: Safety

    2 Safety Safety This technical file does not replace the operating instruc- tions for the voltage regulator. The quick reference guide contains information that will provide a rapid introduction to operating the voltage regulator. ▪ For detailed operation and safety information please read carefully through the voltage regulator operating instructions.
  • Page 8: Hardware

    3 Hardware Hardware Operating controls The device has 15 pushbuttons. The illustration below is an overview of all the device's operating controls.
  • Page 9 3 Hardware Figure 1: Operating controls RAISE key: Sends control command for raise tap- change to the motor-drive unit in manual mode. LOWER key: Sends control command for lower tap- change to the motor-drive unit in manual mode. REMOTE key: Activate/deactivate "Remote" operating mode.
  • Page 10: Display Elements

    3 Hardware NEXT key: Change measured value display and switch to next parameters. ENTER key: Confirm selection and save modified pa- rameters. ESC key: Escape current menu and select previous menu levels. MENU key: Select main menu. F1 to F5 function keys: Select functions displayed on the screen.
  • Page 11 3 Hardware Figure 2: Indicator elements 1 Operating status LED, 9 LED 3, function can be green freely assigned, yellow/ green 2 Overcurrent blocking 10 LED 4, function can be LED, red freely assigned, yellow/red 3 Undervoltage blocking 11 Graphics display LED, red 4 Overvoltage blocking 12 Auto operating mode ac-...
  • Page 12 3 Hardware (only for TAPCON® 230 pro and TAPCON® 230 expert) 6 NORMset active LED, 14 Remote operating mode green active LED 7 LED 1, function can be 15 Lower tap-change active freely assigned, yellow 8 LED 2, function can be 16 Raise tap-change active freely assigned, yellow...
  • Page 13: Functions And Settings

    4 Functions and settings Functions and settings This chapter gives a short summary of all important func- tions and possible settings of the voltage regulator. For details, see the voltage regulator's operating instructions. Before carrying out the parameterization, proceed as fol- lows: If necessary, press at the same time to...
  • Page 14: Normset

    4 Functions and settings > Configuration > General. ð Language Press to select the required language. Press ð The language is set. NORMset NORMset mode is used for quickly starting voltage regu- lation. In NORMset mode, the bandwidth and delay time parameters are automatically adapted to the require- ments of the grid.
  • Page 15 4 Functions and settings A manual tap-change operation is required to activate NORMset. This is how the voltage regulator determines the bandwidth required. If the transformer is switched off, another manual tap- change operation is required. Proceed as follows to activate/deactivate NORMset mode: >...
  • Page 16 4 Functions and settings Press ð The primary voltage is set. Setting the secondary voltage With this parameter, you can set the voltage transform- er's secondary voltage. Proceed as follows to set the secondary voltage: > NORMset > Press until the desired parameter is displayed.
  • Page 17: Control Parameters

    4 Functions and settings Settings in kV are only possible if you have previously entered the parameters for primary and secondary volt- age. Proceed as follows to set the desired value: > NORMset > Press until the desired parameter is displayed. Desired value 1.
  • Page 18: Selecting A Desired Value

    4 Functions and settings Proceed as follows to set the desired value: > Control parameter > voltage regulator > Press until the desired parameter is dis- played. ð Desired value 1/Desired value 2/Desired val- ue 3. If you have already entered the transformer data, press to select the unit you want: "V"...
  • Page 19: Setting Delay Time T1

    4 Functions and settings Proceed as follows to select a desired value: > Control parameter > Voltage regula- tion > Press until the desired parameter is dis- played. ð Active Desired Volt. Level Press to select an active desired value. Press The selected desired value is active.
  • Page 20: Setting Control Response T1

    4 Functions and settings Press ð The delay time T1 is set. 4.3.4 Setting control response T1 You can set the control response as linear or integral. Linear Device responds with a constant delay time which is in- dependent of the control deviation. Integral Device responds with a variable delay time which is de- pendent on the control deviation.
  • Page 21: Setting Delay Time T2

    4 Functions and settings 4.3.5 Setting delay time T2 With this parameter, you can set delay time T2. Delay time T2 is used to compensate for large control devia- tions faster. Proceed as follows to set the delay time T2: >...
  • Page 22: Information About Device

    4 Functions and settings Information about device The info screen displays the following information: To display the info screen, proceed as follows: ► > Info. Info. ð By pressing , the following information screens are al- so displayed: ▪ Measured values ▪...
  • Page 23 4 Functions and settings ▪ IEC 61850 card information Only for TAPCON® 230 pro and TAPCON® 230 expert. Only for TAPCON® 230 expert with CI card. Only for TAPCON® 230 expert with IEC 61850 card.
  • Page 24 5 Overview of parameters Overview of parameters This section contains an overview of the relevant menus and parameters. The availability of individual parameters varies depending on the device ordered. Parameter Setting range Factory setting Current setting NORMset Normset activation On, Off Desired value 1 49...140 V 100 V...
  • Page 25 5 Overview of parameters Parameter Setting range Factory setting Current setting Control parameters > Limit values Undervoltage U< [%] 60...100 % 90 % Delay time U< 0...20 s 10.0 s Undervolt. blocking U< On, Off U< below 30 V On, Off Overvoltage U>...
  • Page 26 5 Overview of parameters Parameter Setting range Factory setting Current setting Primary voltage 0...9,999 kV 0 kV Secondary voltage 57...123 V 100.0 V Primary current 0...10,000 A Current transformer Unknown; 1 A; Unknown connection Transformer circuit see operating in- 0 1PH structions Display kV / V kV, V...
  • Page 27 5 Overview of parameters Parameter Setting range Factory setting Current setting Motor runtime 0...30 s 0.0 s Manual/Automatic Manual, Auto Manual Local/Remote Local, Remote Local Configuration > Parallel operation Parallel operation acti- On, Off vation Parallel operation Circulating reac- Circulating reac- method tive current;...
  • Page 28 5 Overview of parameters Parameter Setting range Factory setting Current setting Max. tap difference 1...4 Follower tapping with- On, Off out U meas Configuration > Customer inputs/outputs GPI 1 – X4:13 see operating in- structions GPI 2 – X4:14 GPI 3 – X4:15 GPI 4 –...
  • Page 29 5 Overview of parameters Parameter Setting range Factory setting Current setting LED2 GPI 2 LED3 yellow LED3 green LED4 yellow LED4 red Configuration > Tap position Tap pos. capture see operating in- structions Analog Val. [%] Tap 0...100 % 0.0 % pos.
  • Page 30 5 Overview of parameters Parameter Setting range Factory setting Current setting Analog value desired 0...100 % 0.0 5 value min Analog value desired 0...100 % 100.0 % value max Minimum desired val- 0...140 V 80.0 V Maximum desired val- 0...140 V 140.0 V Configuration >...
  • Page 31 5 Overview of parameters Parameter Setting range Factory setting Current setting Unsolicited messages On, Off Repeat unsolicited 0...100 messages Appl. confirm. Timeout 1...60 s confirmation RS485 transmit delay 0...254 s time Configuration > Communication interface Network address 0.0.0.0...255.255. 0.0.0.0 255.255 Network mask 0.0.0.0...255.255.
  • Page 32 5 Overview of parameters Only for TAPCON® 230 expert with IEC 61850 card.
  • Page 34 Maschinenfabrik Reinhausen GmbH +49 (0)941 4090-0 Falkensteinstrasse 8 +49(0)941 4090-7001 93059 Regensburg sales@reinhausen.com www.reinhausen.com 4831166/00 ▪ 02/16 ▪...