8 Operation
Linear time response With linear time response, the device responds with a constant delay time
Maschinenfabrik Reinhausen GmbH 2018
A U
is outside the bandwidth. De-
actual
lay time T1 starts.
C U
is outside the bandwidth. De-
actual
lay time T1 starts.
Setting delay time T1
To set the delay time T1, proceed as follows:
1. Go to Settings > Parameters > Control > Delay time T1.
2. Enter delay time T1.
3. Press the Accept button to save the modified parameter.
Selecting time response T1
You can use this parameter to set the time response for delay time T1. You
can select the following options:
▪ Linear time response
▪ Integral time response
regardless of the control deviation.
5252433/02 EN
B U
is within the bandwidth be-
actual
fore delay time T1 is complete.
D U
is still outside the bandwidth
actual
when delay time T1 is complete.
Tap-change operation is initiated.
®
®
ECOTAP
VPD
CONTROL PRO
77