MR ECOTAP VPD CONTROL PRO Operating Instructions Manual page 185

Voltage regulator
Table of Contents

Advertisement

12 Technical data
Maschinenfabrik Reinhausen GmbH 2018
CISPR 11 (EN 55011)
CISPR 16-2-1
CISPR 16-2-3
CISPR 22 (EN 55022)
Table 83: Emitted interference in accordance with IEC 61000-6-4
Environmental durability tests
DIN EN 60529
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-78
ASTM D 4169-09
IEC 60255-21-1 Class
1
IEC 60255-21-2 Class
1
IEC 60255-21-3 Class
1
Table 84: Environmental durability tests
5252433/02 EN
Industrial, scientific and medical equipment - Radio-fre-
quency disturbance characteristics - Limits and methods
of measurement: Class A
Procedure for measuring high-frequency emitted interfer-
ence (radio interference) and immunity - measurement of
conducted emitted interference: Class A
Procedure for measuring high-frequency emitted interfer-
ence (radio interference) and immunity - measurement of
radiated emitted interference: Class A
Information technology equipment - Radio disturbance
characteristics - Limits and methods of measurement:
Class A
Degree of protection IP52 for the front, IP 20 for the rear
Dry cold - 25 °C / 96 hours
Dry heat + 70 °C/ 96 hours
Constant moist heat
+ 40 °C / 93% / 4 days, no dew
Standard Practice for Performance Testing of Shipping
Containers and Systems
DC 3, safety level II
Vibrations (3 cycles, 0.5·g 1 octave/min; 60 cycles, 1.0·g,
1 octave/min)
Shocks (11 ms, 5·g, 15·g, 3 axes)
Earthquakes (1...35 Hz; 3.5 mm/1·g horizontal; 1.5
mm/0.5·g vertical; 1 octave/min, 10 min/axis)