Installing

4.5 Installing the Terminating Module and the Slot Cover

Figure 4-9
4.5
Installing the Terminating Module and the Slot Cover
Properties
● The ET 200iSP distributed I/O station is terminated with the terminating module at the right
hand end of the ET 200iSP. Unless you have inserted a terminating module, the ET 200iSP
is not ready for operation (EMC is not ensured). While the ET 200iSP will start up, removal
of an electronic module will cause a station failure.
● Removal of an electronic module causes a station failure of the ET 200iSP.
● To secure the ET 200iSP mechanically, you must screw the terminating module to the
mounting rail.
● If your ET 200iSP configuration leaves you with a gap in the last slot, you must install a
reserve module or the slot cover in this slot.
– Install a slot cover if the ET 200iSP will not be expanded in the future. The slot cover is
– Install a reserve module if you want to use the free slot for a future expansion (by means
● The terminating module accompanies terminal modules TM-IM/EM and TM-IM/IM.
98
Catch
Uninstalling terminal module TM-EM/EM, starting from the right
integrated in the terminating module.
Replacing the slot cover with an electronic module during operation will cause a station
failure of the ET 200iSP.
of an electronic module).