Installing

4.4 Installing Terminal Modules for the Interface Module and Electronics Modules

4.4
Installing Terminal Modules for the Interface Module and Electronics
Modules
Properties
● The terminal modules are used to accommodate the interface module and the electronic
modules
– TM-IM/EM: The terminal module for the interface module and electronic module is
– TM-IM/IM: Terminal module for 2 interface modules (IM 152 redundancy), located to the
– TM-EM/EM: Terminal module for the electronic modules, located to the right of terminal
– TM-RM/RM: Terminal module for digital output module 2 DO Relay UC60V/2A, located
● The terminal modules can be prewired (without electronic modules).
Requirements
The mounting rail is installed.
Required tools
4.5 mm screwdriver
96
located directly next to the right of terminal module TM-PS-A/ TM-PS-A UC.
right of TM-PS-A/ TM-PS-A UC or TM-PS-B/ TM-PS-B UC.
module TM-IM/EM or TM-IM/IM.
to the right of terminal module TM-IM/EM or TM-IM/IM.
Operating Instructions, 11/2017, A5E00247483-07