Installing A Valve Island With An Interface Module - Siemens SIMATIC ET 200X Manual

Distributed i/o device
Table of Contents

Advertisement

Installation
Installing a FESTO valve island and pneumatic interface module
Prerequisite: You have installed the ET 200X (see Chapter 3.1).
If you want to install a pneumatic interface module or a PM 148 DO 4 DC 24V/2A
power module directly next to a motor starter, the motor starter must be version
w02.
A maximum of six pneumatic interface modules can be plugged into an ET 200X.
To install, perform the followings steps:
1. Slide the pneumatic interface module into the expansion interface of the
preceding module.
2. Tighten the securing screws of the extension interface.
3. Plug the valve island in the interface module.
4. Screw the valve island and the interface module tightly to the rail (see Section
3.1).
Figure 3-9
3-14
4

Installing a valve island with an interface module

5
ET 200X Distributed I/O Device
6
EWA 4NEB 780601602-06