Acyclic Data Transfer Via PROFIBUS DP
Acyclic data exchange takes place between the ET 200iSP and the PG / PC (SIMATIC PDM).
The ET 200iSP receives its parameters using acyclic data exchange. Identification data is also
transferred and displayed in SIMATIC PDM.
● Diagnostics and interrupts (with S7 DP slave and DPV1 slave)
● Data records
DPV0, S7 DP, or DPV1 slave
The ET 200iSP can be operated as a DPV0, S7 DP or DPV1 slave. The following table
compares the functions.
Table 6-1
Function
Parameter assignment and configuration with
GSD file
Configuration and parameter assignment with
HW Config
Cyclic data exchange
Acyclic data traffic (read/write
data record)
● Free access to
● Reassignment of
Diagnostics
● ID-related diagnostics
● Module status
● Channel-related diagnostics
Interrupts
● Diagnostic interrupt
● Hardware interrupt
● Remove/insert interrupt
● Update interrupt
● Time stamping
If you configure the ET 200iSP using the GSD file (in HW Config), you will need SIMATIC PDM for
1
parameter assignment.
For the S7 DP slave, diagnostic and process interrupts are only reported when the CPU is in RUN
2
mode.
ET 200iSP
Operating Instructions, 11/2017, A5E00247483-07
Comparison of DPV0, S7 DP and DPV1
parameters on the field
device
parameters of the
application process
6.1 Basics of commissioning and diagnostics
DPV0
slave
X
X
1
X
Class 1 services
---
(parameter as‐
signment mas‐
ter, e.g. PLC)
Class 2 services
X
(for example,
PD/OP)
X
X
X
---
---
---
---
---
Commissioning and Diagnostics
S7 DP
DPV1
Comment
slave
slave
---
X
X
X
1
X
X
X
X
X
X
One interrupt can be re‐
ported per diagnostic
X
X
frame. For DPV1 and S7
X
X
DP slaves, an interrupt
consists of a slave diag‐
X
X
nostic accompanied by
an acknowledgment
X
X
2
mechanism not inclu‐
ded in DPV0.
X
X
2
X
X
---
X
X
X
135