General technical specifications

8.3 Electromagnetic compatibility, transport and storage conditions

● GL (Germanischer Lloyd)
● LRS (Lloyds Register of Shipping)
● Class NK (Nippon Kaiji Kyokai)
Use of the Distributed I/O Device ET 200iSP in device group I (mining) Category M2
The following conditions must be fulfilled if the ET 200iSP is used in device group I
(underground mining operations and their overground systems) Category M2:
Transport and storage of ET 200iSP
● To avoid ignitable sparks, the Power Supply PS and the mounting rail of the ET 200iSP
● The enclosure in which the ET 200iSP is installed must be approved for device group I,
● Observe all other requirements concerning use of the ET 200iSP in the potentially
8.3
Electromagnetic compatibility, transport and storage conditions
Definition of EMC
Electromagnetic compatibility is the ability of electrical equipment to function satisfactorily in
its electromagnetic environment without influencing this environment.
The ET 200iSP distributed I/O station also meets the requirements of the EMC law of the
European market. This requires that the ET 200iSP distributed I/O system meets the
specifications and directives concerning electrical installation.
Pulseshaped interference
The following table shows the electromagnetic compatibility of the ET 200iSP distributed I/O
station with relation to pulse-shaped interference variables.
Pulse-shaped interference
Electrostatic discharge according to
IEC 61000-4-2.
Burst pulses (high-speed transient interfer‐
ence) to IEC 61000-4-4.
198
CAUTION
must be packaged in shock-proof packaging for transportation and storage (e.g. for
servicing) and immediately removed from the potentially explosive atmosphere.
category M2.
explosive atmosphere given in this manual.
Test voltage
8 kV
6 kV
2 kV (supply line)
2 kV (signal line)
Operating Instructions, 11/2017, A5E00247483-07
corresponds with
degree of severity
3
3
ET 200iSP