How To Connect A Tc Sensor Module - Siemens SIMATIC ET 200iSP Operating Instructions Manual

Distributed i/o
Hide thumbs Also See for SIMATIC ET 200iSP:
Table of Contents

Advertisement

Wiring
5.4 Wiring the ET 200iSP
5.4.10

How to Connect a TC Sensor Module

Properties
The TC sensor module can be used for the internal compensation of the reference junction
temperature. This ships with the 4AI TC.
Prerequisites
The TC sensor module can only be connected to terminal modules with screw terminals.
Required tool
3.5 mm screwdriver
Procedure
1. Insert the TC sensor module into the third terminal row of the terminal module: Terminals
in 3, 7, 11; pin in terminal 15.
2. Tighten the TC sensor module using a 3.5 mm screwdriver. Tighten the screws of terminals
3, 7 and 11.
Figure 5-11
122
TC sensor module
Operating Instructions, 11/2017, A5E00247483-07
ET 200iSP

Hide quick links: