● Resolution (including overrange)
Measured value smoothing
Step:
None
Low
Average
High
Noise suppression, error limits
Interference voltage suppression for f = n x (f1±1%), f1 = interference frequency
● Series mode interference (peak value of disturbance
Crosstalk between inputs
Operational limits (in the entire temperature range, rela‐
tive to the input range)
Basic error limit (operational limit at 25°C, relative to the
input range)
Temperature error (relative to the input range)
Linearity error (relative to the input range)
Repeatability
(in steady state at 25 °C, relative to the input range)
Interrupts
● Limit value interrupt
● Diagnostic interrupt
Diagnostic functions
● Group error display
● Diagnostic information can be read
Monitoring for
● Wirebreak
See EC Prototype Certificate
Input ranges (rated values) / input resistance
● Current
Permissible input current for current input (destruction
limit)
Connection of signal generators
● for current measurement
ET 200iSP
Operating Instructions, 11/2017, A5E00247483-07
< rated input range)
Short-circuit
as 2-wire transducer
13.2 Analog electronics module 4 AI I 2WIRE HART
Technical specifications
12 bits + sign
Yes, can be set in 4 steps
Time constant:
1 x cycle time
4 x cycle time
32 x cycle time
64 x cycle time
min 70 dB
min. - 50 dB
±0.15%
±0.1%
± 0.005%/K
±0.015%
±0.01%
Status, interrupts, diagnostics
Yes, can be set
Yes, can be set
Red "SF" LED
Yes
I
load
I
load
Safety information
KEMA 04ATEX1244
Data for selecting a sensor
4 to 20 mA
90 mA
supported
supported
Analog electronic modules
1
> 25 mA
2
< 3.6 mA
273