IM 152 parameters
Time stamping (enable pa‐
rameter)
2
Edge evaluation event enter‐
ing state
2
Data format
Noise suppression
Temperature unit
Slot reference junction 1 to 2
Input reference junction 1 to 4 ● RTD on channel 0
It may or may not be possible to edit these parameters, depending on the configuration tool used.
1
Can only be assigned in HW Config and if the ET 200iSP is being operated as an S7 DP slave.
2
11.3
Identification and Message Functions (I&M)
Reference
For information on the I&M, refer to the Chapter "Identification data I&M (Page 58)".
11.4

Description of the parameters for the IM 152

11.4.1
Operation at Preset <> Actual Configuration
Description
If the parameter is enabled and:
● a module is removed and inserted during operation, this does not lead to a station failure
of the ET 200iSP.
● the actual configuration differs from the preset configuration, the ET 200iSP continues to
exchange data with the DP master.
ET 200iSP
Operating Instructions, 11/2017, A5E00247483-07
Range of values
● Yes
● No
● rising edge (0-->1)
● falling edge (1-->0)
● Channel-specific
● SIMATIC S7
● 50 Hz
● 60 Hz
● Celsius
● Fahrenheit
● None
● 4 to 35
● RTD on channel 1
● RTD on channel 2
● RTD on channel 3
11.4 Description of the parameters for the IM 152
Default
No
rising edge (0-->1)
SIMATIC S7
50 Hz
Celsius
None
RTD on channel 0
Interface module
Applicability
ET 200iSP
ET 200iSP
ET 200iSP
ET 200iSP
ET 200iSP
ET 200iSP
ET 200iSP