Figure 5-2
Operating the ET 200iSP and PS 120/230 VAC with equipotential bonding
Equipotential bonding EB
Connect the following to the equipotential bonding EB
● The mounting rail of the ET 200iSP system (with the grounding bolts Ex e)
● The terminal module TM-PS-A/ TM-PS-A UC by means of the connection terminal EB
● The terminal module TM-PS-A/ TM-PS-A UC by means of the connection terminal EB
● Mounting rail for mounting the cable shields (with an Ex e-terminal)
According to EN 60 079-14, equipotential bonding is mandatory in hazardous areas.
For more information on the equipotential bonding system, refer to the System Manual
"Principles of explosion protection
12521844)".
ET 200iSP
Operating Instructions, 11/2017, A5E00247483-07
DANGER
It is not permitted to connection the equipotential bonding EB to the PE conductor of the
supply system.
5.2 Operating the ET 200iSP with equipotential bonding
(http://support.automation.siemens.com/WW/view/en/
Wiring
107