Siemens SIMATIC ET 200iSP Operating Instructions Manual page 322

Distributed i/o
Hide thumbs Also See for SIMATIC ET 200iSP:
Table of Contents

Advertisement

Analog electronic modules
13.11 Parameters of the analog electronic modules
Parameters for configuration "4AO I HART"
Table 13-37 Parameters for configuration "4AO I HART"
Group diagnostics
Diagnostics: wire break
Diagnostics: wire break
Output range
Response to CPU/ master STOP
Substitution value
The substitute values are stored in the flash memory of the IM 152. These are output at the
next startup of the ET 200iSP until it starts exchanging data with the DP master.
Remember this behavior if you change to a different project engineering environment with
the ET 200iSP.
Solution: Erase the flash memory of the IM 152 first.
Parameters for configuration "...I +x"
In addition to the "4AO I HART" configuration, the following parameters can be set for the
"...I +x" configurations:
Table 13-38 Parameters for configuration "I +x"
Parameter
HART retries (number of retries)
HART Fast Mode
322
Parameter
WARNING
0 to 10
● enabled
● disabled
Range of values
● enabled
● disabled
● enabled
● disabled
● enabled
● disabled
● Disabled
● 0 mA to 20 mA
● 4 mA to 20 mA
● HART
● Zero output
current/voltage
● Set substitution
value
● Hold last value
Every value of the
nominal range
Range of values
Operating Instructions, 11/2017, A5E00247483-07
Default
Applicability
enabled
Module
enabled
Channel
enabled
Channel
HART
Channel
Set substitution
Channel
value
0 to 20 mA: 0 mA
Channel
4 to 20 mA and
HART: 4 mA
Default
Applicability
2
Module
disabled
Module
ET 200iSP