Commissioning and Diagnostics

6.4 Assigning Parameters for the ET 200iSP during Operation using SIMATIC PDM

How to set parameters for all modules of the ET 200iSP
1. Select the first remote I/O object (ET 200iSP in the left pane of the SIMATIC Manager),
right-click and select the Open Objects menu command. In the next dialog, "SIMATIC PDM
Select Device", select SIEMENS > ET 200iSP > Head-end Station and confirm with "OK".
2. In the next dialog, select "Specialist" as the user and confirm with "OK".
3. Upload all parameters of the modules (menu command File > Complete Upload to PG/PC).
4. Set the parameters for all required modules. In the left-hand pane of the SIMATIC PDM
window, you can select all the modules of the ET 200iSP.
5. Save the changes (menu command File > Save) so that the file is updated.
6. Download all parameters to the modules (menu command Device > Complete Download
to Device). Close SIMATIC PDM.
Reference
For more detailed information on parameter assignment, refer to the documentation and online
help of SIMATIC PDM.
6.4
Assigning Parameters for the ET 200iSP during Operation using
SIMATIC PDM
Properties
● Using the parameter assignment function, you can also assign module parameters during
operation with SIMATIC PDM. Each new parameter setting that is correct is adopted by the
module and stored in non-volatile memory.
● Bad parameters are ignored. The module then retains the previous parameter settings.
● If the modules are restarted (after turning the supply voltage of the ET 200iSP off ---> on),
the current parameter assignment in the non-volatile memory of the modules is applied
(SF LED of the modules is off).
● Adopting the retentive parameter settings on modules takes place regardless of the
communication between the ET 200iSP and the DP master.
● The outputs of the modules are controlled by the class 1 DP master.
Requirements
SIMATIC PDM Version 6.0 or higher (integrated or stand-alone version)
Procedure for Reassigning Parameters
1. Start SIMATIC PDM.
2. Open the project.
140