Wiring
5.4 Wiring the ET 200iSP
Required tools
3.5 mm screwdriver
Procedure
1. Strip the insulation from the wires to the sensors / actuators.
2. Secure the individual wires in the screw or spring terminals.
Figure 5-8
Pin assignment, see Chapter "Terminal modules TM-EM/EM 60S and TM-EM/EM 60C
(Page 213)".
Note
The inputs and outputs of the ET 200iSP distributed I/O station are intrinsically safe.
Disconnecting wires to the sensors, actuators, and HART field devices on the terminal module
TM-EM/EM is permitted during operation in zone 1 and zone 2. In zone 21 and zone 22, you
may only open the enclosure of the ET 200iSP when no explosive dust is present!
118
Terminal module TM-EM/EM
Connector for the electronic module:
channel 0 to 3, or
channel 0 to 7
Wiring the terminal module TM-EM/EM
Operating Instructions, 11/2017, A5E00247483-07
ET 200iSP