Configuring Counters - Siemens SIMATIC ET 200iSP Operating Instructions Manual

Distributed i/o
Hide thumbs Also See for SIMATIC ET 200iSP:
Table of Contents

Advertisement

Configuration options
3.16 Counting
Figure 3-10
32-bit down counter (cascading counter function)
The maximum counting range is always 4294967295 to 0.
The principle of operation is identical to that of the 16-bit down counter. Channel 1 has no
function.
3.16.3

Configuring counters

Procedure in HW Config
Drag the required configuration "2 Count/ 6 DI NAMUR" or "2 Count/ 6 Control" from the
hardware catalog to the configuration table with the mouse or set the configuration with the
parameters.
"2 Count/ 6 DI NAMUR" configuration:
● Assignment of the digital inputs on electronic module 8 DI NAMUR
Additional information on pin assignment is available in the Digital electronics module 8 DI
NAMUR (Page 235).
72
Principle of operation of the 16-bit down counter
Operating Instructions, 11/2017, A5E00247483-07
ET 200iSP

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents