Siemens SIMATIC ET 200iSP Operating Instructions Manual page 139

Distributed i/o
Hide thumbs Also See for SIMATIC ET 200iSP:
Table of Contents

Advertisement

6. Now select the icon labeled "PROFIBUS DP Network", right-click and select Insert new
object > Remote I/O. Make the following entries in the dialog that opens:
Name: Name of the ET 200iSP station (for example, ET 200iSP).
Address: PROFIBUS address you set on the interface module.
Number of "Remote I/O" objects: Number of ET 200iSP stations for which you are setting
parameters.
Confirm with "OK". Result: The ET 200iSP station is now displayed in the right-hand pane
of the window.
7. Now select the remote I/O object you created in the previous step (ET 200iSP), right-click
and select the Insert New Object > Remote I/O Module menu command. Make the following
entries in the dialog that opens:
Name: Name of the module (for example, 8 DI NAMUR).
Address: Slot of the first electronic module in the ET 200iSP station (4).
Number of "Remote I/O Objects: Number of electronic modules in the ET 200iSP station.
Confirm with "OK". Result: The electronic modules are now displayed in the right-hand pane
of the window.
8. Select the first remote I/O object (electronic module in the left pane of the SIMATIC
Manager), right-click and select the Open Objects menu command. In the next dialog,
"SIMATIC PDM Select Device", select SIEMENS > ET 200iSP > Modules and confirm with
"OK".
9. From the next dialog box, select "Specialist" as the user and confirm with "OK." In this
mode, you can assign parameters. Result: SIMATIC PDM is started.
10.Once SIMATIC PDM has started, select the relevant electronic module as the "module
type". Then click in one of the gray fields to update the window. Result: The parameters
and I&M of the electronic module are displayed.
11.Now set the parameters of the electronic module. Save the changes with the File > Save
menu command and download the parameters to the electronic module with the Device >
Download to Device menu command. Close SIMATIC PDM.
12.Follow the same procedure as described in points 8 through 11 for each of the ET 200iSP
objects (electronic modules).
Procedure for assigning parameters to the interface module
1. Select the first remote I/O object (ET 200iSP in the left pane of the SIMATIC Manager),
right-click and select the Open Objects menu command. In the next dialog, "SIMATIC PDM
Select Device", select SIEMENS > ET 200iSP > Head-end Station and confirm with "OK".
2. From the next dialog box, select "Specialist" as the user and confirm with "OK." In this
mode, you can assign parameters. Result: SIMATIC PDM is started.
3. Now set the parameters of the interface module. Save the changes with the File > Save
menu command and download the parameters to the interface module with the Device >
Download to Device menu command. Close SIMATIC PDM.
ET 200iSP
Operating Instructions, 11/2017, A5E00247483-07
6.3 Project Engineering with GSD File and SIMATIC PDM
Commissioning and Diagnostics
139