Siemens SIMATIC ET 200iSP Operating Instructions Manual page 237

Distributed i/o
Hide thumbs Also See for SIMATIC ET 200iSP:
Table of Contents

Advertisement

Pin assignment of a single contact with 10 kΩ load resistance (mechanical NO contact)
Table 12-3
Pin assignment of a single contact with 10 kΩ load resistance (mechanical NO contact)
Pin assignment and view
Pin assignment of a single, changeover contact with 10 kΩ (mechanical normally open contact)
Table 12-4
Pin assignment of a closed changeover contact with 10 kΩ (mechanical changeover contact)
Pin assignment and view
ET 200iSP
Operating Instructions, 11/2017, A5E00247483-07
Digital electronic modules
12.1 Digital electronics module 8 DI NAMUR
Remarks
Single contact 1:
Channel 0: Terminals 1 and 2
Single contact 2:
Channel 1: Terminals 5 and 6
Single contact 3:
Channel 2: Terminals 9 and 10
Single contact 4:
Channel 3: Terminals 13 and 14
Single contact 5:
Channel 4: Terminals 3 and 4
Single contact 6:
Channel 5: Terminals 7 and 8
Single contact 7:
Channel 6: Terminals 11 and 12
Single contact 8:
Terminals 15 and 16
DI: Input signal
V
: Sensor supply
S
Remarks
Changeover contact 1:
Channel 0: Terminals 1 and 2
Channel 1: Terminal 5
Changeover contact 2:
Channel 2: Terminals 9 and 10
Channel 3: Terminal 13
Changeover contact 3:
Channel 4: Terminals 3 and 4
Channel 5: Terminal 7
Changeover contact 4:
Channel 6: Terminals 11 and 12
Channel 7: Terminal 15
DI: Input signal
V
: Sensor supply
S