Siemens SIMATIC ET 200iSP Operating Instructions Manual page 226

Distributed i/o
Hide thumbs Also See for SIMATIC ET 200iSP:
Table of Contents

Advertisement

Power Supply
10.2 Power supply PS 120/230 VAC
Output current for 120 VAC (85 VAC to 132 VAC) and
ambient temperature
● From -20°C to +70°C with horizontal installation and
● from -20°C to +60°C with horizontal installation
● -20°C to +50°C with horizontal installation
Status display
Interrupts
Diagnostic functions
● Group error display
● Diagnostic information can be read
See EC-type-examination certificate
U
M
Available soon
1
Tolerance range 85 VAC to 264 VAC.
2
Fusing with 6 A automatic circuit breaker and tripping characteristic C (for each ET 200iSP station)
Rated current: 0.75A (for 120 VAC)/ 0.45A (for 230 VAC)
3
You can find additional information about in the section "Restricted Number of Connectable Electronics
4
Modules (Page 52)"
Note
Take appropriate measures to ensure that U
226
-20°C to +50°C for all other installation positions
Technical specifications
max. 3A
max. 4A
max. 5A
Status, interrupts, diagnostics
yes (on IM 152)
No
No
yes (over IM 152)
Safety data
KEMA 09ATEX0156
264V DC, 264V AC
= 264 VDC, 264 VAC is not exceeded.