1. Installation

1.3.5 Connecting with the fieldbus plug from Festo

1-28
Note
Use protective caps or blanking plugs to seal unused
connections. You will then achieve protection class IP65.
Observe the assembly instructions for the fieldbus plug.
Tighten the two fastening screws at first by hand and then
with max. 0.4 Nm!
With the fieldbus plug from Festo (FBS-SUB-9-BU-2x5POL-B),
you can connect the CPX terminal easily to the fieldbus. You
can disconnect the plug from the node without interrupting
the bus line (T-TAP function).
Note
The clamp strap in the Festo fieldbus plug is connected
only capacitively internally with the metal housing of the
sub-D socket. This prevents equalizing currents from flow­
ing via the screening of the fieldbus cable (Fig. 1/7).
Clamp the screening of the fieldbus cable under the
clamp strap in the fieldbus plug.