3. Diagnostics
Byte 0
Byte 1
Error code
Bit
Significance
0
Generic error
1
Current
2
Voltage
3
4
Communication error
5 ... 6
7
Manufacturer specific
bold = Bit is used by CPX terminal
Tab. 3/12: Error register (index 1001 with bit assignment as per CiA 301/401)
Festo P.BE-FB14-EN en 1411d English
Byte 2
Byte 3
Error re­
Status bits
gister
Index 1001
Index 1002 (manufacturer status register)
Explanation
Bit is set for each error
– Short circuit/overload in sensor supply
– Short circuit/overload at the outputs
– U
OUT
– U
VAL
– Failure of load voltage at CPX output module or CPX
input module
– Node guard, heart beat, CAN error
– Wire break
– Other error
Further diagnostic information is provided by the CPX
terminal in bytes 3 ... 6 of the emergency object
(manufacturer status register, index 1002).
Byte 4
Byte 5
CPX
CPX error
module
no.
no.
(undervoltage at the outputs)
(undervoltage at valves)
Byte 6
Byte 7
Reserved
Additional
error inf.
3-17