Festo CPX-FB14 Description page 26

Terminal cpx, bus node, canopen networkprotocol
Hide thumbs Also See for CPX-FB14:
Table of Contents

Advertisement

1. Installation
1-12
Setting the error mode with DIL switch
You set the error mode with switch element 1 of the dual DIL
switch 2:
Error mode
Reporting undervoltage error
Filtering undervoltage error
Errors during monitoring of the
operating and load voltage
supplies will be ignored
Reserved
Tab. 1/2:
DIL switch 2 ("Undervoltage" error message)
With the setting "Filter undervoltage error", voltage errors
which occur will not be reported as errors. In this way, you
can, for example, suppress unnecessary error messages
during the commissioning phase.
The setting of the DIL switch has precedence especially over
the parameterisation of defined settings. No emergency mes­
sage is transmitted with error filtering.
2
Setting DIL switch 2
2.1: OFF
(factory setting)
2.1: ON
2.2: Always OFF
Festo P.BE-FB14-EN en 1411d English