Siemens Sinamics G110M Original Instructions Manual page 332

Distributed converter for simogear geared motors
Hide thumbs Also See for Sinamics G110M:
Table of Contents

Advertisement

Appendix
A.9 Electromagnetic Compatibility
Table A- 16
EMC Phenomenon
Conducted emissions
(disturbance voltage)
Radiated emissions
Harmonic Currents
Table A- 17
Typical Harmonic Current (% of rated input current) at U
Note
Units installed within the category C2 (domestic) environment require supply authority
acceptance for connection to the public low-voltage power supply network. Please contact
your local supply network provider.
Units installed within the category C3 (industrial) environment do not require connection
approval.
332
Conducted disturbance voltage and radiated emissions
Converter type
Remark
All converters with integrated class A filters.
Order number:
6SL3517-1BE**-*A**
Converter frame sizes A and B with integrated class A
filter.
Order number:
6SL3517-1BE11-*A*0
6SL3517-1BE12-*A*0
6SL3517-1BE13-*A*0
6SL3517-1BE14-*A*0
6SL3517-1BE16-*A*0
6SL3517-1BE17-*A*0
6SL3517-1BE21-*A*0
In a domestic environment this product may cause
radio interference in which case supplementary miti-
gation measures may be required.
Harmonic Currents
5th
7th
11th
24
11
K
13th
17th
9
7
Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
Level acc. to
IEC 61800-3
Category C2
First Environment -
Professional Use
Category C2
First Environment -
Professional Use
1 %
19th
23rd
6
5
SINAMICS G110M Operating Instructions
25th
4
4

Advertisement

Table of Contents
loading