Fault buffer of actual values
The inverter saves the time, fault code and fault value for every fault it receives.
Figure 11-5
r0949 and r2133 contain the fault value - important for diagnostics - as "fixed point" or
"floating point" number.
The "fault time received" is in parameter r2130 (in complete days) as well as in parameter
r0948 (in milliseconds referred to the day of the fault). The "fault time removed" is written to
parameters r2109 and r2136 when the fault has been acknowledged.
The inverter uses its internal time calculation to save the fault times. More information on the
internal time calculation can be found in Chapter System runtime (Page 210).
If an additional fault occurs before the first fault has been acknowledged, then this is also
saved. The first alarm remains saved. The fault cases that have occurred are counted in
p0952. A fault case can contain one or several faults.
Figure 11-6
The fault buffer can accept up to eight actual faults. The next to last fault is overwritten if an
additional fault occurs after the eighth fault.
Figure 11-7
SINAMICS G110M Operating Instructions
Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
Saving the first fault in the fault buffer
Saving the second fault in the fault buffer
Complete fault buffer
Alarms, faults and system messages
11.2 Faults
291