EMC Immunity
The SINAMICS G110M drives have been tested in accordance with the immunity
requirements of category C3 (industrial) environment:
Table A- 18
EMC Phenomenon
Electrostatic Discharge (ESD)
Radio-frequency Electromagnet-
ic Field
Amplitude modulated
Fast Transient Bursts
Surge Voltage
1.2/50 μs
Conducted
Radio-frequency Common Mode
Mains Interruptions & Voltage
Dips
Voltage Distortion
Voltage Unbalance
Frequency Variation
Commutation Notches
A.10

Mistakes and improvements

If you come across any mistakes when reading this manual or if you have any suggestions
for how it can be improved, then please send your suggestions to the following address or by
E-mail:
Siemens AG
Digital Factory
Motion Control
Postfach 3180
91050 Erlangen, Germany
E-mail (mailto:docu.motioncontrol@siemens.com)
SINAMICS G110M Operating Instructions
Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
EMC Immunity
Standard
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6
EN 61000-4-11
EN 61000-2-4
EN 61000-2-4
EN 61000-2-4
EN 60146-1-1
A.10 Mistakes and improvements
Level
4 kV Contact discharge
8 kV Air discharge
80 MHz ... 1000 MHz
10 V/m
80 % AM @ 1 kHz
2 kV @ 5 kHz
1 kV differential (L-L)
2 kV common (L-E)
0.15 MHz ... 80 MHz
10 V/rms
80 % AM @ 1 kHz
95 % dip for 3 ms
30 % dip for 10 ms
60 % dip for 100 ms
95 % dip for 5000 ms
10 % THD
3 % Negative Phase Se-
quence
Nominal 50 Hz or 60 Hz
(± 4 %)
Depth = 40 %
Area = 250 % x degrees
Appendix
Performance
Criterion
A
A
A
A
A
A
C
C
D
A
A
A
A
333