Switchover Between Different Settings - Siemens Sinamics G110M Original Instructions Manual

Distributed converter for simogear geared motors
Hide thumbs Also See for Sinamics G110M:
Table of Contents

Advertisement

The reports and the machine documentation can also be found in the section: Acceptance
tests for the safety functions (Page 325).
8.11

Switchover between different settings

There are applications that require different inverter settings.
Example:
You connect different motors to one inverter. Depending on the particular motor, the inverter
must operate with the associated motor data and the appropriate ramp-function generator.
Drive data sets (DDS)
Your can set several inverter functions differently and then switch over between the different
settings.
The associated parameters are indexed (index 0, 1, 2, or 3). Using control commands select
one of the four indexes and therefore one of the four saved settings.
The settings in the inverter with the same index are called the drive data set.
Figure 8-53
SINAMICS G110M Operating Instructions
Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
Switching over between different settings using drive data sets (DDS)
8.11 Switchover between different settings
Functions
259

Advertisement

Table of Contents
loading

Table of Contents