Siemens Sinamics G110M Original Instructions Manual page 174

Distributed converter for simogear geared motors
Hide thumbs Also See for Sinamics G110M:
Table of Contents

Advertisement

Functions
8.4 Setpoint sources
Interconnecting the fixed speeds with a main setpoint
Figure 8-12
Table 8- 5
Parameter
p1070 = 1024
Select fixed setpoint by direct or binary selection
The converter distinguishes between two methods for selecting the fixed setpoints:
1. Direct selection:
You set 4 different fixed setpoints. By adding one or more of the four fixed setpoints, up
to 16 different resulting setpoints are obtained.
Figure 8-13
Additional information about direct selection can be found in function diagram 3011 in the
List Manual.
2. Binary selection:
You set 16 different fixed setpoints. You precisely select one of these 16 fixed setpoints
by a combination of four selection bits.
174
Fixed speeds as setpoint source
Setting the fixed speed as a setpoint source
Remark
Main setpoint
Interconnecting the main setpoint with fixed speeds.
Simplified function diagram for directly selecting fixed setpoints
SINAMICS G110M Operating Instructions
Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD

Advertisement

Table of Contents
loading

Table of Contents