Functions

8.10 Safe Torque Off (STO) safety function

8.9.7.3

((Load monitoring - responses 0 ... 8))

Table 8- 24
p2181 = 0
p2181 = 1
p2181 = 2
p2181 = 3
p2181 = 4
p2181 = 5
p2181 = 6
p2181 = 7
p2181 = 8
The settings in p2193 for pumps/fans (p2193 = 4 or 5) are only permissible with the settings
for load monitoring for pumps/fans (p2181 = 7 or 8)
Example
You can find an example for using the free function blocks in Chapter Fundamentals
(Page 321).
Application description for the free function blocks
See also: Function Manual
(https://support.industry.siemens.com/cs/gb/en/view/60467055/29243398027)
See also
Example (Page 323)
8.10
Safe Torque Off (STO) safety function
These operating instructions describe the commissioning of the STO safety function when it
is controlled via a fail-safe digital input.
You will find a detailed description of all safety functions and control using PROFIsafe in the
Safety Integrated Function Manual, see Section Manuals and technical support (Page 334).
242
Response options for load monitoring
Load monitoring deactivated (factory setting)
A07920 for torque/speed too low
A07921 for torque/speed too high
A07922 for torque/speed out of tolerance
F07923 for torque/speed too low
F07924 for torque/speed too high
F07925 for torque/speed out of tolerance
Pump/fan load monitoring as alarm
Pump/fan load monitoring as fault