Siemens Sinamics G110M Original Instructions Manual page 284

Distributed converter for simogear geared motors
Hide thumbs Also See for Sinamics G110M:
Table of Contents

Advertisement

Service and maintenance
10.5 Firmware downgrade
Procedure
To downgrade the inverter's firmware to an older version, proceed as follows:
1. Switch off the 24 V inverter power supply voltage.
If the inverter is equipped with a module for the internal 24 V power supply, then instead
of the 24 V power supply, you must switch off the 400 V supply.
2. Remove the Power Module.
3. Insert the card with the matching firmware into the slot on the lower side of the Power
Module until you can feel it snap into place.
4. Mount the Power Module with the inserted firmware card.
5. Switch on the 24 V inverter supply voltage.
If the inverter is equipped with a module for the internal 24 V power supply, then instead
of the 24 V power supply, you must switch on the 400 V supply.
6. The inverter transfers the firmware from the memory card into its memory.
The transfer takes between 5 and 10 minutes.
While data is being transferred, the LED RDY on the inverter stays red. The BF LED
flashes orange with a variable frequency.
284
SINAMICS G110M Operating Instructions
Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD

Advertisement

Table of Contents
loading

Table of Contents