Control And Status Word 1 - Siemens Sinamics G110M Original Instructions Manual

Distributed converter for simogear geared motors
Hide thumbs Also See for Sinamics G110M:
Table of Contents

Advertisement

Figure 7-3
The telegrams use - with the exception of telegram 999 (free interconnection) - the word-by-
word transfer of send and receive data (r2050/p2051).
If you require an individual telegram for your application (e.g. for transferring double words),
you can adjust one of the predefined telegrams via parameters p0922 and p2079. For
details, please refer to the List Manual, function diagrams 2420 and 2472.
7.4.1.1

Control and status word 1

Control word 1 (STW1)
Bit
0
1
SINAMICS G110M Operating Instructions
Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
Interconnection of the receive words
Significance
Telegram 20
All other tele-
grams
0 = OFF1
0 → 1 = ON
0 = OFF2
1 = No OFF2
7.4 PROFIdrive profile for PROFIBUS and PROFINET
Explanation
The motor brakes with the ramp-down time
p1121 of the ramp-function generator. The
inverter switches off the motor at standstill.
The inverter goes into the "ready" state. If, in
addition bit 3 = 1, then the inverter switches on
the motor.
Switch off the motor immediately, the motor
then coasts down to a standstill.
The motor can be switched on (ON com-
mand).
Configure fieldbus
Signal inter-
connection
in the in-
verter
p0840[0] =
r2090.0
p0844[0] =
r2090.1
135