Siemens Sinamics G110M Original Instructions Manual page 240

Distributed converter for simogear geared motors
Hide thumbs Also See for Sinamics G110M:
Table of Contents

Advertisement

Functions
8.9 Application-specific functions
Monitoring, pump/fan
The monitoring functions for pumps and fans are similar. The blocking protection applies
equally to both applications.
For pumps, there is also a leakage monitoring function.
Principle of operation
Within speed thresholds 1 and 3, the inverter monitors the torque and the speed for pumps
and fans.
If the torque or the speed moves, for longer than the time set in p2192, in the ranges of
blockage, leakage or dry running protection/belt breakage, then the response defined in
p2181 is realized.
240
SINAMICS G110M Operating Instructions
Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD

Advertisement

Table of Contents
loading

Table of Contents