Settings For Know-How Protection - Siemens Sinamics G110M Original Instructions Manual

Distributed converter for simogear geared motors
Hide thumbs Also See for Sinamics G110M:
Table of Contents

Advertisement

● Switching to the control panel (complete control panel functionality: Fetch master control,
all buttons and setting parameters)
● Upload (only parameters that are accessible even though know-how protection is active)
The individual parameters that are excluded from the know-how protection can be found in
the List Manual in Chapter "Parameters for write protection and protection of know-how".
Commissioning the converter with know-how protection
Procedure - overview
1. Commission the converter.
2. Create the exception list (Page 275).
3. Activate the know-how protection (Page 273).
4. Save the settings in the converter by copying RAM to ROM with
5. Save the project with
(machine type, password, etc.) that may be required for the support of the end customer.
9.4.2.1

Settings for know-how protection

Activating know-how protection
Preconditions
● You are online.
If you have created a project offline on your computer, you must download it to the
inverter and go online.
● You have inserted the recommended Siemens card. See also Section: Commissioning
tools (Page 29).
SINAMICS G110M Operating Instructions
Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
on the PG/PC. Also back up any other project-related data
Data backup and series commissioning
9.4 Write and know how protection
or via p0971 = 1.
273