Interconnecting the fieldbus with the main setpoint
Figure 8-9
Most standard telegrams receive the speed setpoint as a second process data PZD2.
Table 8- 2
Parameter
p1070 = 2050[1]
p1075 = 2050[1]
8.4.3
Electromechanical potentiometer
The SINAMICS PM240M power module has a perma-
nently hardwired electromechanical potentiometer.
The potentiometer is permanently active and is, by de-
fault the main setpoint source.
When the main setpoint source is set to fieldbus, for ex-
ample when using PROFIBUS or PROFINET communi-
cations, the potentiometer is disabled.
The default setting for the electromechanical potentiome-
ter is Unipolar voltage input (0 V ... +3 V).
Note
Parameters related to parameter p0756 modification
When changing p0756 , the parameters of the scaling characteristic (p0757, p0758, p0759,
p0760) are overwritten with the following default values:
For p0756 = 0, 1, 4, p0757 is set to 0.0 V, p0758 = 0.0 %, p0759 = 10.0 V and p0760 =
100.0 %.
For p0756 = 2, p0757 is set to 0.0 mA, p0758 = 0.0 %, p0759 = 20.0 mA and p0760 =
100.0 %.
For p0756 = 3, p0757 is set to 4.0 mA, p0758 = 0.0 %, p0759 = 20.0 mA and p0760 =
100.0 %.
SINAMICS G110M Operating Instructions
Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
Fieldbus as setpoint source
Setting the fieldbus as setpoint source
Remark
Main setpoint
Interconnect the main setpoint with process data PZD2 from the fieldbus.
Additional setpoint
Interconnect the additional setpoint with process data PZD2 from the fieldbus.
Functions
8.4 Setpoint sources