To change an existing address of a slave, the following procedure should be performed:
1.
2.
3.
4.
5.
6.
7.
SINAMICS G110M Operating Instructions
Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD
Plug the AS-i Programmer into the addressing socket of the Inverter
Turn the dial on the Programmer to the ADDR posi-
tion. The display will indicate that this mode has
been selected.
Press the
button; the screen will display uSE
and the number of the lower addressed slave.
The existing slave addresses are shown at the bot-
tom of the display.
Press the
and
Press the
button; the display now shows SEt.
The selected number will begin to flash.
Press the
and
slave address number.
Press the
button to confirm the new address.
ProG is displayed briefly followed by confirmation of
the address change.
buttons to select the slave address number to be changed.
buttons to select the new
Commissioning
5.2 Basic commissioning
115