Indicates that the normal current limits are active. The drives display will flash AC.Lt to indicate that normal current limits are active.
10.10
Regenerating
Bit
SP
Coding
1
Range
OFF(0) or On(1)
Update rate
Background
Indicates that power is being transferred from the motor to the drive.
10.11
Dynamic brake active
Bit
SP
Coding
1
Range
OFF(0) or On(1)
Update rate
Background
Indicates that the braking IGBT is active. If the IGBT becomes active this parameter is held on for at least 0.5s so that it can be seen on the display.
10.12
Braking resistor alarm
Bit
SP
Coding
1
Range
OFF(0) or On(1)
Update rate
Background
This parameter is set when the braking IGBT is active and the braking energy overload accumulator is greater than 75% (Pr 10.39). This parameter is
held on for at least 0.5s so that it can be seen on the display.
10.13
Direction commanded
Bit
SP
Coding
1
Range
OFF(0) or On(1)
Update rate
Background
This parameter is set if the pre-ramp reference (Pr 1.03) is negative (reverse), reset if pre-ramp reference is positive (forward).
10.14
Direction running
Bit
SP
Coding
1
Range
OFF(0) or On(1)
Update rate
Background
This parameter is set if the post-ramp reference (Pr 2.01) is negative (reverse), or reset if post-ramp reference is positive (forward).
10.15
Mains loss detected
Bit
SP
Coding
1
Range
OFF(0) or On(1)
Update rate
Background
Indicates that the drive has detected mains loss from the level of the DC bus voltage. This parameter can only become active if mains loss ride
through or mains loss stop modes are selected (see Pr 6.03 on page 88).