Load Defaults; Security Status - Emerson 2202 Advanced User's Manual

Commander sk series ac variable speed drive for 3 phase induction motors from 0.25kw to 110kw, 0.33hp to 150hp
Table of Contents

Advertisement

Parameter
Parameter
Introduction
x.00
description format
Parameter number
2.08
Standard ramp voltage
4.07, 21.29
Current limits
5.07, 21.07
Motor rated currents
5.09, 21.09
Motor rated voltages
5.10, 21.10
Motor rated power factor
5.17, 21.12
Stator resistances
5.18
Switching frequency
5.23, 21.13
Voltage offsets
5.24, 21.14
Transient inductances
6.06
DC injection braking current
NOTE
If parameter copying is enabled when no SmartStick is installed into the drive, the drive's display will show a C.Acc trip.
NOTE
The SmartStick should be fully inserted or removed from the drive before a drive reset is performed.
11.43

Load defaults {29}

Bit
SP
Coding
Range
no(0), Eur(1), USA(2)
Default
no(0)
Update rate
Actioned on exit of edit mode or drive reset
If this parameter is set to a non-zero value and edit mode is exited or the drive is reset when the drive is inactive, the selected default parameters will
automatically be loaded. After the parameters have been set to default values they are automatically saved to the drive's internal EEPROM. If the
drive is active the display will flash FAIL once and then Pr 11.43 will be set back to no.
Value
Display
0
no
No action
1
Eur
Load European defaults
2
USA
Load USA defaults
Disconnect the electro-mechanical brake circuit before performing a default.
WARNING
11.44

Security status {10}

Bit
SP
Coding
Range
L1(0), L2(1), L3(2), LoC(3)
Default
L1(0)
Update rate
Actioned on exit of edit mode
This read write parameter defines the level of security for menu 0.
Value
Level
0
L1
Only the first ten parameters can be accessed.
1
L2
Parameters up to 60 can be accessed.
2
L3
Parameters up to 95 can be accessed.
Lock security, so that the security code must be entered before a parameter can
3
LoC
be edited and set security status to L1.
The LED keypad can adjust this parameter even when user security is set.
Commander SK Advanced User Guide
Issue Number: 9
Keypad and
Serial
display
communications
Function
FI
DE
Txt VM DP ND
1
Function
FI
DE
Txt VM DP ND
1
1
Access permitted
www.controltechniques.com
CT Modbus
PLC Ladder
RTU
programming
RA
NC
NV
PT
US RW BU
1
1
RA
NC
NV
PT
US RW BU
1
1
Advanced parameter
CTSoft
Menu 0
descriptions
PS
1
PS
1
Menu 11
149