Status Relay Source; Terminal B3 Mode Select; Terminal B7 Mode Select - Emerson 2202 Advanced User's Manual

Commander sk series ac variable speed drive for 3 phase induction motors from 0.25kw to 110kw, 0.33hp to 150hp
Table of Contents

Advertisement

Parameter
Menu 8
Introduction
x.00
8.27

Status relay source

Bit
SP
Coding
Range
Pr 0.00 to Pr 21.51
Default
Pr 10.01
Update rate
Read on drive reset
This parameter defines the parameter to be represented by the status relay. Only valid parameters can be selected as a source for the relay output. If
a non-valid parameter is programmed, then the relay will remain in the de-energized state.
8.28 to 8.30
Unused parameters
8.31

Terminal B3 mode select

Bit
SP
Coding
Range
in(0), out(1), Fr(2), PuLS(3)
Default
out(1)
Update rate
Background
This parameter selects the function of Terminal B3 as follows:
Value
Display
0
in
1
out
2
Fr
3
PuLS
If modes 1, 2 or 3 are selected, the digital input operation of the terminal is disabled.
In modes 0 and 1, terminal B3 will function as digital input/outputs which are described in menu 8.
In modes 2 and 3, terminal B3 will function as a frequency output or a PWM output as described in menu 3.
The frequency output will be scaled automatically to the source parameter. For example, with a source parameter of Pr 1.21 equal to 100 and an
output frequency of 10kHz (Pr 3.18), when the value of Pr 1.21 is 50, the output frequency will be 5kHz.
Examples
From default, setting Pr 8.31=Fr, will give a 5kHz output with a 50Hz reference value, when Pr 8.21=2.01 (with Pr 8.41=USEr). By setting the scaling
(Pr 3.17) to 0.01, this will give an output of 50 pulses/sec. With a 50Hz reference value.
From default, setting Pr 8.31=PuLS, will give a 24V output with a 50Hz reference value, when Pr 8.21=2.01 (Pr 8.41=USEr). By feeding this PWM
output into a R/C network, a voltage output can be obtained. This output would be almost proportional to the frequency output of the drive.
8.32 to 8.34
Unused parameters
8.35

Terminal B7 mode select {34}

Bit
SP
Coding
Range
dig(0), th(1), Fr(2), Fr.hr(3)
Default
dig(0)
Update rate
Background
This parameter selects the function of Terminal B7 as follows:
Value
Display
0
dig
1
th
2
Fr
3
Fr.hr
High resolution frequency input
If modes 1, 2 or 3 are selected, the digital input operation of the input is disabled.
In mode 0, the digital input functions as described in menu 8.
In mode 1, the input functions as a motor thermistor (PTC type).
Trip resistance: 3kΩ
Reset resistance: 1k8
The drive will not trip if the thermistor goes short circuit.
116
Parameter
Keypad and
description format
display
FI
DE
Txt VM DP
ND
2
FI
DE
Txt VM DP
ND
1
Function
Digital input
Digital output
Frequency output
PWM output
FI
DE
Txt VM DP
ND
1
Function
Digital input
Thermistor input
Frequency input
www.controltechniques.com
Serial
CT Modbus
PLC Ladder
communications
RTU
programming
RA NC
NV
PT
US RW BU
1
1
1
RA NC
NV
PT
US RW BU
1
1
RA NC
NV
PT
US RW BU
1
1
Advanced parameter
CTSoft
Menu 0
PS
1
PS
1
PS
1
Commander SK Advanced User Guide
Issue Number: 9
descriptions

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents