Stator Resistance; Maximum Switching Frequency; High Stability Space Vector Modulation - Emerson 2202 Advanced User's Manual

Commander sk series ac variable speed drive for 3 phase induction motors from 0.25kw to 110kw, 0.33hp to 150hp
Table of Contents

Advertisement

Parameter
Menu 5
Introduction
x.00
5.17

Stator resistance

Bit
SP
Coding
0.000 to 65.000 Ω
Range
Default
0.000
Second motor
Pr 21.12
parameter
Update rate
Background
This parameter contains the stator resistance of the machine for open loop vector mode operation.
If the drive cannot achieve the necessary current levels to measure the stator resistance during an auto-tune (e.g. there is no motor connected to the
drive) an rS trip will occur and the value in Pr 5.17 remains unchanged. If the necessary current levels can be achieved but the calculated resistance
exceeds the maximum allowable value for that particular drive size, an rS trip will occur and Pr 5.17 will contain the maximum allowable value.
5.18

Maximum switching frequency {37}

Bit
SP
Coding
Range
3(0), 6(1), 12(2), 18(3) kHz
Default
3(0)
Update rate
Background
Value
Display
0
3
1
6
2
12
3
18
This parameter defines the required switching frequency.
The drive may automatically reduce the actual switching frequency (without changing this parameter) if the power stage becomes too hot. The
switching frequency can reduce from 18kHz to 12kHz to 6kHz to 3kHz. An estimation of the IGBT junction temperature is made based on the heatsink
temperature and an instantaneous temperature drop using the drive output current and switching frequency. The estimated IGBT junction
temperature is displayed in Pr 7.34.
If the temperature exceeds 135
frequency change mode is enabled (see Pr 5.35 on page 82) to reduce the drives losses and thus reduce the IGBT junction temperature.
If the load condition persists, the junction temperature may continue to rise. If the temperature exceeds 145
reduced the drive will initiate an O.ht1 trip.
Every 20ms the drive will attempt to restore the set switching frequency if the higher switching frequency will not take the IGBT temperature above
o
135
C.
Also refer to 10.18 on page 131.
NOTE
The 18kHz switching frequency is not available on Commander SK size B and C, 400V units, Commander SK size D or Commander SK size 2 to 6.
Therefore it is not recommended to use these drives where the output frequencies are likely to be above 550 Hz.
NOTE
With drive firmware V01.07.01 onwards, the 400V size C drive will have an actual switching frequency of 3kHz when the output frequency is below
6Hz.
With a default switching frequency of 3 kHz, the maximum output frequency should be limited to 250Hz. Ideally a minimum ration of 12:1 should be
maintained between the output frequency and the switching frequency. This ensures the number of switching per cycle is sufficient to ensure the
output waveform quality is maintained at a minimum level.
5.19

High stability space vector modulation

Bit
SP
Coding
1
Range
OFF(0) or On(1)
Default
OFF(0)
Update rate
Background
0: OFF High stability space vector modulation disabled
1: On
High stability space vector modulation enabled
80
Parameter
Keypad and
description format
display
FI
DE
Txt VM DP
ND
3
FI
DE
Txt VM DP
ND
1
Frequency (kHz)
3
6
12
18
o
C, the switching frequency is reduced if possible (i.e if the current switching frequency is >3kHz) and auto-switching
FI
DE
Txt VM DP
ND
www.controltechniques.com
Serial
CT Modbus
PLC Ladder
communications
RTU
programming
RA NC
NV
PT
US RW BU
1
1
1
RA NC
NV
PT
US RW BU
1
1
1
RA NC
NV
PT
US RW BU
1
1
Advanced parameter
CTSoft
Menu 0
PS
1
PS
1
o
C and the switching frequency cannot be
PS
Commander SK Advanced User Guide
Issue Number: 9
descriptions